Stainless Steel
Pressure Transmitter is designed to meet the needs and
requirements of the refrigeration and building automation
industries. The SA series stainless steel construction makes the
transmitter ideally suited to resist the effects of corrosive
media such as ammonia, freon, and steam. The SA Series features a
stainless steel moisture-sealed case that protects the electronics
from harsh environmental conditions.
| SPECIFICATIONS |
| Supply
voltage |
| Standard |
9-24 VDC @ 15 mA |
| Option T |
22-27 VDC @ 50 mA |
| Accuracy* |
±1% full scale output
from best fit |
|
straight line, including
nonlinearity, repeatability, and hysteresis |
|
*Option T adds
0.3% of span. |
| Thermal effect |
|
| Zero |
Less than ±1% of full
scale output per 100°F |
|
(55°C) over compensated
range |
| Span |
Less than ±1% of
reading per 100°F (55°C) over compensated range |
| Output |
| Standard |
1-5 VDC ±0.1 VDC |
| Option T |
4-20 mA |
| Max overpressure |
2 x rated pressure (100,
200, 300 psig |
|
or models up to 2068 kPa); |
|
1.5 x rated pressure
(500, 1000, 3000, 5000 psig or models up to 34475 kPa); |
| Burst |
10 x rated pressure
(100, 200, 300 psig or models up to 2068.5 kPa); |
|
5 x rated pressure (500,
1000, 3000, 5000 psig or models up to 34,475 kPa) |
| Temp ratings |
|
| Operating |
-67° to 212°F (-55°
to 100°C) |
| Compensated |
32° to 176°F (0° to
80°C) |
| Wetted parts |
300 series stainless
steel |
| Shock |
50G, 5 ms |
| Vibration |
20.6G rms, 15-200 Hz |
Selection: To
Order

Lower pressure ranges available by
request
|
|